Basic configuration table of 7200gs series of motor soft starter
(I) wiring schematic diagram
the figure is the standard wiring legend of 7200gs frequency converter. Now the following description is made for the figure:
(1) is the isolation wire, which is the isolation stranded wire
(2) terminal 15: output +15v, maximum 20mA
(3) the seals at the end form different angles. 13 and 14 cannot be used at the same time (when used at the same time, the frequency commands are added)
(4) terminal symbol: ◎ represents the main circuit terminal, and ○ represents the control circuit terminal
(5) multi function analog output is the special analog output of indicator such as frequency meter. Please do not use it as feedback control of the control system. If you need to use the feedback signal, you can choose the optional interface card (ao-12 card)
(II) terminal strip description
1 Main circuit terminal
see table for the description of main circuit terminal strip
table main circuit terminal strip description
horsepower terminal mark
440v 25hp220v 25 ~ 100hp440v 30 ~ 400hp
r/l1 main circuit power input s/l2t/l3u/t1 frequency converter output v/t2w/t3b1/p ● b1/Rockwell hardness tester features p-b2: external brake resistance ● b1/p- ⊝: DC power input
- B2 - ⊝ ● ⊕ - ⊝: DC power input or external brake detection module ⊝.8853; - E () grounding terminal (the third kind of grounding, the grounding resistance is less than 100 Ω) 2 Control circuit terminal
see table for the description of control circuit terminal strip
table control loop terminal block description
type number name terminal function signal level operation
input
signal
number
1 operation/stop "close" → forward rotation, "open" → stop DC 24V, 8Ma optocoupler isolation 2 reversal/stop "close" → reverse, "open" → stop 3 external abnormal input "close" → abnormal, "On" → normal 4 abnormal reset "off" → reset continuation table
type number name terminal function signal level operation
input
signal
number
5 main/auxiliary speed switch "off" → auxiliary frequency command DC 24V, 8Ma optocoupler isolation 6 multi segment speed command 2 "close" → multi segment speed command 2 is valid 7 inch command "close" → inch operation 8 external BB "close" → frequency converter stops outputting 111 ~ 8 common end - analog
input
signal
No.
15 speed command power supply speed command setting power terminal +15v, 20mamax13 main speed frequency command 0 ~ 10V/100% frequency 0 ~ +10v (20k Ω) 144 ~ 20mA/100% frequency 4 ~ 20mA (250 Ω) 16 auxiliary frequency command 0 ~ 10V/100% frequency 0 ~ +10v (10K Ω) 17 common end terminals 13, 14, 16 frequency command common end - 12 mask stranded wire terminal connection isolation stranded wire shield sheath - operation
output
signal
number
9 signal output during operation (no)
.capacity of terminal conducting contact during operation: 250VAC, 1A
30VDC, 1A
1025 zero speed detection minimum frequency (cn-07) below is low level open collector output: 48V, 50mA
26 speed consistent detection set frequency within ± 1% is low level 27 terminal 25, 26 common end - 18 abnormal output signal: no
: NC
abnormal: terminal closed terminal open
contact capacity: 250VAC, 1A
30VDC, 1A below
1920 analog output
21 frequency meter output 0 ~ 10V/100% frequency 0 ~ 10V, Max 2mA below 22 common terminal note terminals ⑤ ~ ⑧, ⑨ ~ ⑩, (21) ~ (22), and (25) ~ (27) are factory settings
(III) internal wiring of main circuit
7200gs series inverter internal wiring of main circuit of various models is shown in the figure
(IV) fuse free circuit breaker (QF) shall be installed between AC power supply and r.s.t of power input terminal of 7200gs, and electromagnetic contactor (km) shall be installed as required. If the leakage circuit breaker is installed for leakage fault protection, in order to prevent the misoperation of the leakage circuit breaker, select the one with the sensitivity current of more than 200mA and the action time of more than 0.1s. See table for common components of external wiring of main circuit
Table wiring appliance selection table
220V 7200gs frequency converter cable (mm2) fuse free switch ③
electromagnetic contactor ③ maximum applicable horsepower HP (kw)
rated (kVA)
rated current (a)
main circuit ① grounding wire e[g]
control wire ② 25 (18.5) 5~2TO-225S(150A)
CN-8030(22). 5 ~ 2to-225s (175A)
cn-100 continued table
220V 7200gs frequency converter cable (mm2) fusionless switch ③
electromagnetic contactor ③ maximum applicable horsepower HP (kw)
rated (kVA)
rated current (a)
main circuit ① grounding wire e[g]
control line ② 40 (30) 5~2TO-225S(175A)
CN-12 550(37) × 2P220.5~2TO-225S(200A)
CN-15060(45) × 2P220.5~2TO-225S(225A)
CN-18075(55) × 2P300.5~2TO-400S(300A)
CN-300100(75) × 2p500.5 ~ 2to-400s (400A)
cn-300440v grade 7200gs frequency converter cable (mm2) fuse free switch ③
electromagnetic contactor ③ maximum applicable horsepower HP (kw)
rated (kVA)
rated current (a)
main circuit ① grounding wire e[g]
control wire ② 25 (18.5) 5~2TO-100S(75A)
CN-5030(22). 5~2TO-100S(100A)
CN-5040(30). 5~2TO-100S(100A)
CN-6550(37). 5~2TO-125S(125A)
CN-8060(45). 5~2TO-225S(175A)
CN-10075(55). 5~2TO-225S(175A)
CN-125100(75) × 2P220.5~2TO-225S(225A)
CN-150125(90) × 2P300.5~2TO-400S(300A)
CN-300150(110) × 2P300.5~2TO-400S(300A)
CN-300175(132) × 2P500.5~2TO-400S(400A)
CN-300215(160) × 2P500.5~2TO-400S(400A)
CN-300250(185) × 2P500.5~2TO-600S(600A)
S-K400④(450A)
300(220) × 2p600.5 ~ 2td-800s (800A)
s-k600 ④ (800A)
① the power line includes r/l1, s/l2, t/l3, u/t1, v/t2, w/t3, (+), (-)
② the control line is the terminal wiring of the control base plate
③ the QF and KM types in the table are Taian product numbers, and other brands with the same rating can also be used. In order to reduce noise interference, please remember to install R-C shock absorbers at both ends of KM coil, such as La to GA mass ratio, molecular weight, material shape and structure, etc. (0.1 μ f/1000VDC,10Ω/5W)。
④ the KM type in the table is Mitsubishi product number, and other brands with the same rating can also be used
figure 7200gs soft starter main circuit internal wiring diagram of various models
(V) external wiring precautions
1 Control circuit wiring
(1) control circuit wiring must be separated from 4. Open loop control and closed loop control main circuit wiring (r/l1, s/l2, t/l3, u/t1, v/t2, w/t3) and other power lines to avoid noise interference
(2) contact output terminals ⑨, ⑩, (18), (19), (20) must be separated from ① ~ ⑧, (21), (22), (25), (26), (27) and (11) ~ (17)
(3) in order to prevent noise interference, the control circuit wiring must use shielded isolation stranded wires. Please refer to the figure, and the wiring distance cannot exceed 50m
2. Main circuit wiring
(1) input power r/l1, s/l2, t/l3, do not need to consider the phase sequence relationship
figure processing diagram of isolated stranded wire (shielded wire)
(2) the input power supply cannot be connected to the output terminals u/t1, v/t2, w/t3 of the frequency converter
(3) the output terminals u/t1, v/t2 and w/t3 of the frequency converter are connected to the terminals u/t1, v/t2 and w/t3 of the motor. If the frequency converter executes the forward rotation command and the motor reverses, it is only necessary to switch any two lines of the motor u/t1, v/t2 and w/t3
figure the connection method of multiple grounding wires of multiple frequency converters
(4) the output end of the frequency converter must not be connected with capacitors or LC, RC noise filters used to improve the power factor
3. The grounding wire
(1) the grounding terminal (E) is grounded in the third way (the grounding resistance is less than 100 Ω)
(2) the grounding wire of frequency converter cannot be grounded together with high current loads such as electric welding machine and high-power motor, and must be grounded separately
(3) the size of the grounding wire depends on the technical standard of electrical equipment. The shorter the grounding wire, the better
(4) when multiple frequency converters are grounded together, please refer to the figure and do not form a grounding circuit